34-52 07/13
2. STANDARD FEATURES AND EQUIPMENT
2.1 Performance
Up to 94% efficiency at low fire with low return temp
Inward-fired burner technology with seamless modulation capable of 10-to-1 turndown
Low NOx emissions - SCAQMD compliant ≤15 ppm (no derate or efficiency reduction to obtain ≤15 ppm)
Ducts direct combustion air up to 100 equivalent feet through 6" diameter material (requires UL approved
vent cap, see optional equipment list)
Vents up to 100 equivalent feet through 6" diameter material (UL approved vent cap supplied)
2.2 Burner, Combustion Controls & Operating Controls
Pre-mix, surface burner with proportional gas/air control and variable speed blower motor
Electronic ignition control with pre– and post-purge
Electronic operating control with digital readout
Firing cycle status panel lights
Indicating light for flame failure with remote indication contacts
Dual temperature limits with manual-reset on high-limit temperature control
Manual-reset, electronic low-water cutoff with test switch (no lockout on power loss)
Pressure gauge on tank
High and low gas pressure switches
CSD-1 compliant, FM compliant
Intertek / ETL listed to U.S. and Canadian standards
Maximum 240°F operating limit
Combustion air filter
2.3 Analog or Network BAS Interface to Individual Boilers (connection options to multiple boiler controls
differ from connection options to individual boilers)
Modbus protocol on operating control through a 485 serial connection (optional cable required)
Remote on/off terminals
Remote 4-20mA or 0-10V modulation control terminals(this is for motor drive and not for loop reset)
2.4 Warranty and Service Policy (see warranty or service policy for details)
Ten-year pressure vessel workmanship, materials and thermal shock warranty