1
34-53 08/14
VT.3
®
WATER BOILER
INSTALLATION & MAINTENANCE MANUAL
Models (1500, 1800, 2000) WB 250A-IF
Installation and service must be performed by a qualified service installer, service agency or the gas supplier.
IMPORTANT: THIS MANUAL CONTAINS INFORMATION REQUIRED FOR INSTALLATION, OPERATION AND MAINTENANCE
OF THIS EQUIPMENT. READ AND FOLLOW THE INFORMATION IN THIS MANUAL AND ALL OTHER PROVIDED
INSTRUCTIONS, LABELS AND MARKINGS BEFORE INSTALLING, OPERATING OR SERVICING THIS UNIT.
TO THE INSTALLER: After installation, these instructions must be given to the equipment user or left near the appliance.
SPECIAL INSTRUCTIONS TO THE OWNER: Retain this manual for future reference. These instructions contain important
information that will help you in maintaining and operating this appliance.
Riverside Hydronics
®
, LLC
990 Haltom Road
Fort Worth, Texas 76117
1-800-990-5918
www.riversidehydronics.com
Vista de pagina 0
1 2 3 4 5 6 ... 37 38

Indice de contenidos

Pagina 1 - WATER BOILER

1 34-53 08/14 VT.3® WATER BOILER INSTALLATION & MAINTENANCE MANUAL Models (1500, 1800, 2000) WB 250A-IF Installation and service must be pe

Pagina 2

10 34-53 08/14 5.5 Gas Connection 1. Safe operation of unit requires adequate gas supply with the required static and dynamic (flow) pressures. Act

Pagina 3

11 34-53 08/14 WARNING – Adequate clean combustion air must be provided to the appliance. Under no circumstances should the appliance ever be under

Pagina 4 - PRODUCT SAFETY INFORMATION

12 34-53 08/14 Vertical Remote Air (recommended) Horizontal Remote Air (allowed) 6.5 Remote Air Consideration for Combined Remote Air Ducting

Pagina 5 - (Locations May Vary)

13 34-53 08/14 • A barometric damper (draft control) is supplied with all models, unless the CAT34 option is ordered. If the boiler was ordered wit

Pagina 6

14 34-53 08/14 • Obtain the correct adapter for attaching and sealing to the VT3 5-7/8 inch vent connection outlet from the manufacturer of the lis

Pagina 7

15 34-53 08/14 7.3.2 Vertical or Horizontal Vent Termination 1. The vent terminal must have a minimum clearance of 4 feet (1.22 m) horizontally fr

Pagina 8

16 34-53 08/14 8 OPERATING AND SAFETY CONTROLS 8.1 Operating Temperature Control An adjustable digital operating control is located in the fron

Pagina 9

17 34-53 08/14 9 TEMPTRAC™ ELECTRONIC CONTROLLER PANEL 9.1 Principle Of Operation The boiler operates to satisfy the setpoint of the TempTrac dig

Pagina 10 - 34-53 08/14

18 34-53 08/14 LABEL DEFAULT VALUE NET TEMPERATURE NET TEMP DETERMINED BY St1 165 165°F LED display value Hy1 -8 157°F St1 + Hy1 St4 -10 15

Pagina 11

19 34-53 08/14 • D: The unit will remain in modulation until the sensed temperature rises above 155°F (St4). The firing rate returns to low fire. M

Pagina 12

2 34-53 08/14 TABLE OF CONTENTS 1. Safety Considerations 2. Product Description 3. Boiler Installation 3.1 Checking Equipment Before You Insta

Pagina 13

20 34-53 08/14 10 BOILER CONTROL INTERFACE A terminal strip for the remote connection is located behind the hinged control panel at the top of the

Pagina 14

21 34-53 08/14 10.4 Making BMS/BAS remote connections for analog and binary (on/off) signals A terminal strip for the remote connection is located

Pagina 15

22 34-53 08/14 • Outside Air Temperature Sensor Installation - The wire leads for the outdoor sensor should be connected to the TempTrac control

Pagina 16

23 34-53 08/14 3. Call For Heat - If the TempTrac operating control senses a call-for-heat condition: a. The High Gas Pressure and low Gas Pressur

Pagina 17

24 34-53 08/14 9. Flame Safeguard LED Diagnostic Indicator - If the Fenwal Flame Safeguard Control at any time during the operating sequence senses

Pagina 18

25 34-53 08/14 12.5 Startup Procedure 1. Carefully study the burner start-up information included in this manual. 2. Fill system tank with water.

Pagina 19

26 34-53 08/14 NOTE: After a modification, it will be possible to enter the Modulation output setting without entering the password for 10min. Afte

Pagina 20

27 34-53 08/14 INLETPRESSUREMANIFOLDPRESSUREVALVE ORIFICEADJUSTMENTREGULATORADJUSTMENT Gas Train Illustration REGULATORADJUSTMENTHIGH GAS PRESSUR

Pagina 21

28 34-53 08/14 13 TROUBLESHOOTING GUIDE Problem Probable Cause Corrective Action Starting or Pre-purge Failure Power Supply Check fuse and/or

Pagina 22

29 34-53 08/14 14 REPLACEMENT PARTS REPLACEMENT PARTS

Pagina 23

3 34-53 08/14 9. TempTrac Controller Panel 9.1 Principle of Operation 9.2 Upper LED Readout 9.3 Lower LED Readout 9.4 Control Buttons 9

Pagina 24

30 34-53 08/14 14.1 Control Panel

Pagina 25

31 34-53 08/14 14.2 Control Panel Components (Optional components may not be included) Key No. Part No. Description Qty. U/M 1 101947 CONT

Pagina 26

32 34-53 08/14 14.3 Burner Assembly

Pagina 27 - Gas Train Illustration

33 34-53 08/14 14.4 Burner Assembly and Gas Train Components Optional components may not be included) Burner Assembly Components Item Qty Pa

Pagina 28

34 34-53 08/14 15 PERIODIC MAINTENANCE Listed below are items that must be checked to ensure safe reliable operations. Maintenance must be performed

Pagina 29 - REPLACEMENT

35 34-53 08/14 6. The combustion air filter should be replaced every six months. If filter blockage becomes excessive the filter safety switch will

Pagina 30

36 34-53 08/14 16 RECOMMENDED MAINTENANCE SCHEDULE 1. Annual Maintenance a. Check all joints and pipe connections for tightness, corrosion or dete

Pagina 31

37 34-53 08/14 NOTES:

Pagina 32 - 14.3 Burner Assembly

38 34-53 08/14 MODEL NUMBER: SERIAL NUMBER: INSTALLATION DATE: Riverside Hydronics, LLC • 990 Haltom Road • Ft. Worth, TX 76117 • 1

Pagina 33

4 34-53 08/14 1. SAFETY CONSIDERATIONS WARNING: If the information in the supplied manual(s) is not followed exactly, a fire, explosion or exposu

Pagina 34

5 34-53 08/14 2 PRODUCT DESCRIPTION Component, Controls and Connection Locations (Locations May Vary)

Pagina 35 - NOMINAL FILTER SIZE

6 34-53 08/14 3 BOILER INSTALLATION 3.1 Checking Equipment Before You Install Inspect the unit completely upon receipt from the freight carrier b

Pagina 36

7 34-53 08/14 4 GENERAL PIPING GUIDELINES Consult factory for piping of hybrid boiler systems that contain both condensing and non-condensing boile

Pagina 37

8 34-53 08/14 4.4 Filling The Boiler 1. Fill the system with water. To be sure that the unit is not “air bound,” open the relief valve. Leave the

Pagina 38 - Riverside Hydronics

9 34-53 08/14 *Multiplier for Propane: 1.57 **Multiplier for alternate pressure drops: 0.3" W.C. 0.77; 1.0" W.C. 1.41; 2.0" W.