LABEL DEFAULT VALUE NET TEMPERATURE NET TEMP DETERMINED BY
St1
165 165°F LED display value
Hy1
-8 157°F St1 + Hy1
St4
-10 155°F St1 + St4
SR
-10 145°F St1 + St4 + SR
• St1: The system’s desired maximum setpoint (when all firing ceases). This is the temperature setpoint of the
appliance. The factory setpoint is 165°F.
• Hy1: The differential from St1. This is the Burner-On threshold. The burner Call-For-Heat is initiated and
establishes the firing rate at low fire. The factory default is -8°F and is adjustable to -1°F.
This is the drop in temperature °F below the setpoint that the boiler must drop for the heat load to re-establish
following a heat cycle (heat cycle; heat load is established, unit comes on, heat load is satisfied, unit goes
off). Boiler will hold at low fire until parameter St4 is reached; causing burner to modulate higher or parameter
St1 is reached; causing the burner to shutoff.
• St4: The Modulation Threshold. This additional differential from the St1 setting is the value when the change
from low fire to modulation occurs. The factory default setting is -10
°F and is field adjustable.
• SR: The Modulation Band. This parameter is added to the St4 setting and establishes the lower end
temperature of the modulation range where the burner will be operating at 100% of rate. The firing rate will
increase or decrease proportionately between 100% and low fire depending upon the differential between this
setpoint and St4. If loop temperature drops below the modulation range, boiler will hold at high fire. The
factory default setting is -10
°F and is field adjustable.
• A to B: A system with a setpoint of 165°F (St1) has a heating demand placed upon it and the system
temperature begins to fall. No action.
• B: If the sensed temperature at Probe-1 falls to 157°F (Hy1), the “BURNER ON THRESHOLD” is activated.
This initiates the burner Call-for-Heat with a firing rate established at low fire.
• B to C: If further temperature fall occurs, approaching 155°F, the firing rate remains at low fire.
• C: Temperature drop at 155°F (St4) enters the “MODULATION THRESHOLD”.
• C to D: Once modulation is established, the sensed loop temperature can fluctuate between 155°F and
145°F (between St4 and SR). The firing rate increases or decreases proportionately between 100% and low
fire, depending upon the temperature sensed in the return loop. Temperature rise in the heat exchanger
varies accordingly, 45° to 15° depending upon the firing rate.