34-53 08/14
6. The combustion air filter should be replaced every six months. If filter blockage becomes excessive the filter
safety switch will not allow the burner to fire. To avoid nuisance shutdown in dirty environments, check and
replace filter more frequently. See Filter Replacement Illustration below for removal detail.
7. Inspect low water cutoffs and relief valves for proper operation at every six months, or more often if indicated
by inspection.
8. Keep appliance area clear and free from combustible materials, gasoline and other flammable vapors and
liquids.
9. Check frequently to be sure the flow of combustion and ventilation air is unobstructed to the appliance.
10. When electrical controls are serviced or replaced refer to ELECTRICAL COMPONENT LOCATIONS for
identification and location of components.
11. All replacement parts are available through your Riverside Hydronics
®
Dealer. If you need assistance
identifying or contacting your local dealer, you may contact Riverside Hydronics directly at the address and
telephone number located on the first and last page of this manual.
12. If the appliance is to be shut down for an extended period of time, the primary gas valve and the water supply
should be shut off. When the appliance is returned to service, a thorough inspection of all utilities and general
appliance condition should be conducted.
FILTER REPLACEMENT ILLUSTRATION
REMOVE FILTER BOX
ACCESS COVER TO
REPLACE FILTER.
NOMINAL FILTER SIZE
12 X 24 PLEATED