D: The unit will remain in modulation until the sensed temperature rises above 155°F (St4). The firing rate
returns to low fire. Modulation will only reactivate when return loop temperature drops to 155°F.
E to F: Low fire is maintained if the return loop temperature ranges between 155° and 165°F.
F: This firing pattern will continue until the temperature reaches the “Burner OFF” threshold of 165°F (St1)
and shuts off.
9.6 To View The Setpoint
Push and release the SET key to see the set point value.
To return to normal display, press SET + UP or wait 15 seconds without pressing any key.
9.7 To Change The Setpoint
Push the SET key. The upper display will show the “St1” parameter name, while the lower display will show
its value.
Use the UP or DOWN key to cycle through the parameter names.
Push the SET key to modify a parameter value. The value starts flashing in the lower display.
To change it push the UP or DOWN keys. Push the SET key again to confirm the value and pass to the
setting of next set point.
Repeat the operations described at points 3, 4, 5.
To Exit: press SET + UP or wait 15 seconds without pressing any key
NOTE: Each point has a time out of 15 seconds. If any key is pushed within 15 seconds the controller exits the
set points programming procedure.
NOTE: The set value is stored even when the procedure is exited by waiting the time-out to expire.
9.8 To Change Other Parameters
Push the SET and DOWN arrow simultaneously for 3 seconds.
Select the required parameter. The name of the parameter is on the upper display; its value is on the lower
display.
Press the SET key: the value of the parameter will start blinking.
Use UP or
DOWN to change the value.
Press SET to store the new value and move to the following parameter.
To Exit: Press SET + UP or wait 15s without pressing a key.
9.9 LED Display Alarm Messages
Alarm messages are displayed in t upper LED readout and alternate with the default display. An alarm LED ICON is
also illuminated. (See TempTrac User Manual 34-80 for full description)